| Customization: | Available |
|---|---|
| Theory: | Conrol Relay |
| Usage: | Household Appliances Relay |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Technical parameters | M460 | M265 |
| Function | Monitoring 3-phase voltage | |
| Monitoring terminals | L1-L2-L3 | L1-L2-L3-N |
| Supply terminals | L1-L2 | L1-N |
| Voltage range | 220-230-240-380-400-415-440-460(P-P) | 127-132-138-220-230-240-254-265(P-N) |
| Ranted supply frequency | 45Hz-65Hz | |
| Measuring range | 176V-552V | 101V-318V |
| Threshold adjustment voltage | 2%-20% of Un selected | |
| Adjustment of asymmetry threshold | 5%-15% | |
| Hysteresis | 2% | |
| supply indication | green LED | |
| Time delay | Adjustable 0.1s-10s,10% | |
| Measurement error | ≤1% | |
| Run up delay at power up | 0.5s time delay | |
| Konb setting accuracy | 1% of scale value | |
| Reset time | 1000ms | |
| Temperature coecient | 0.05%/ºC,at=20ºC(0.05%ºF,at=68ºF) | |
| Output | 1×SPDT | |
| Current rating | 10A/AC1 | |
| Switching voltage | 250VAC/24VDC | |
| Min.breaking capacity DC | 500mW | |
| Output indication | red LED | |
| Mechanical life |
1×107 |
|
| Electrical life(AC1) | 1×106 | |
| Operating temperrature | -20ºC to +55ºC(-4ºF to 131ºF) | |
| Storage temperature | -35ºC to +75ºC(-22ºF to 158ºF) | |
| Mounting/DIN rail | Din rail EN/IEC 60715 | |
| Protecting degree | IP40 for front panel /IP20 terminals | |
| Operating position | any | |
| Overvoltage category | III. | |
| Pollution degree | 2 | |
| Max.cable size(mm²) | soild wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG 12) | |
| Dimensions | 90×18×64mm | |
| Weight | 64g | |
| Standards | IEC/EN 60255-1,IEC/EN61010-1 | |