Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | DR-45-5 | DR-45-12 | DR-45-15 | DR-45-24 | |
OUTPUT |
DC VOLTAGE | 5V | 12V | 15V | 24V |
RATED CURRENT | 5A | 3.5A | 2.8A | 2A | |
CURRENT RANGE | 0-5A | 0-3A | 0-2.8A | 0-2A | |
RATED POWER | 25W | 36W | 40W | 48W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | |
VOLTAGE ADJ. RANGE | 4.75-5.5V | 10.8-13.2V | 13.5-16.5V | 21.6-26.4V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 800ms, 60ms,50ms/230VAC at full load | ||||
HOLD UP TIME (Typ.) | 100ms/230VAC 21 ms/115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120-370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
EFFICIENCY (Typ.) | 72% | 77% | 77% | 80% | |
AC CURRENT (Typ.) | 0.88A/115VAC 0.48A/230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 15A/115VAC,30A/230VAC | ||||
PROTECTION | OVERLOAD | 105 -160% rated output power | |||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | |||||
OVERVOLTAGE | 5.75-6.75V | 13.8-16.2V | 17.25-20.25V | 27.6 -32.4V | |
Protection type: Shut down o/p voltage, re-power on to recover | |||||
ENVIRONMENT | WORKING TEMP. | -10ºC ~ +50ºC (Refer to "Derating Curve") | |||
WORKING HUMIDITY | 20 - 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85"C, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03%/"C (0 ~ 50'C) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1 cycle, period for60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | Design refer to EN50178 | |||
WITHSTAND VOLTAGE | l/P-0/P:1.5KVAC l/P-FG:1.5KVAC 0/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | l/P-0/P:100M Ohms / 500VDC / 25'C/ 70% RH | ||||
EMC EMISSION | Compliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3 | ||||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | ||||
OTHERS | MTBF | 441,5K hrs min. MIL-HDBK-217F (25'C) | |||
DIMENSION | 78*93*56mm (W*H*D) | ||||
PACKING | 0.27Kg; 45pcs/14Kg/1.02CUFT | ||||
NOTE | 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 "c of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. 3.Tolerance : includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |