Customization: | Available |
---|---|
Theory: | Voltage Relay |
Usage: | Communication Relay |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
• It serves to control supply voltage for appliances sensitive to supply tolerance, protection of the device against under/over voltage.
• DV2-1G is fixed settings,DV2-1T Adjustable settings over / under voltage relay. For difference settings of over / under voltage.
• 3-state indication - LEDs indicating normal state and 2 fault states.
• Supply from monitored voltage (monitors level of its own supply).
• 2-MODULE, DIN rail mounting.
|
DV2-1G
|
DV2-1T
|
||
Supply
|
||||
Supply terminals
|
L1-N
|
L1/L2/L3/N
|
||
Voltage range
|
145-300 V AC 50 - 60 Hz
|
|||
Burden
|
AC max.1.2VA/
0.5W
|
120-127-132-138-220
230-240-254-265-277
|
||
Max. dissipated power
(Un + terminals)
|
6W
|
|||
Upper level(Umax)
|
AC265V
|
AC225-275V
|
||
Bottom level(Umin)
|
AC175V
|
AC165-215
|
||
Max. permanent
|
AC300V
|
|||
Peak overload<1ms
|
AC450V
|
|||
Time delay
|
0.1s
|
adjustable 0-10s
|
||
Accuracy
|
||||
Set. accuracy (mechanical)
|
5 %
|
|||
Repeat accuracy
|
< 1 %
|
|||
Dependance on temperature
|
< 0. 1 % / °C (°F)
|
|||
Tolerance of limit values
|
5 %
|
|||
Hysteresis
(from fault to normal)
|
5V
|
3% of adjusted value
|
||
Output
|
|
|||
Number of contacts
|
1x NO/SPST
|
1x NO/SPST
|
1x NO/SPST
|
1x NO/SPST
|
Current rating
|
40 A / AC1
|
50 A / AC1
|
63 A / AC1
|
80 A / AC1
|
Breaking capacity(AC1)
|
10000 VA
|
12500 VA
|
15750 VA
|
20000 VA
|
Inrush current(<3s)
|
50 A
|
63 A
|
80 A
|
100 A
|
Switching voltage
|
250V AC1
|
|||
Output indication
|
red / yellow LED
|
|||
Mechanical life
|
3x10^7
|
|||
Electrical life (AC1)
|
0.7x10^5
|
|||
Other informatio
|
||||
Operating temperature
|
- 30 °C to 70 °C
|
|||
Storage temperature
|
- 45 °C to 85 °C
|
|||
Electrical strength
|
4kV (supply - output)
|
|||
Operating position
|
any
|
|||
Mounting
|
DIN rai EN 60715
|
|||
Protection degree
|
IP40 from front panel/IP20 terminals
|
|||
Overvoltage category
|
III.
|
|||
Pollution degree
|
2
|
|||
Max. cable size (mm^2)
|
solid wire max. 1x 2.5 or 2 x 1.5 /
with sleeve max. 2x 1.5 (AWG 14 )
|
|||
Dimensions
|
90x36x70mm
|
|||
Weight
|
145g
|
145g
|
145g
|
145g
|
Standards
|
IEC60947-5-1 EN 60255-6, EN 61010-1
|
|||
Packing Details
|
Box DIM: 520x225x175, QTY: 50Pcs, GW:8.2kg
|