Customization: | Available |
---|---|
Theory: | Voltage Relay |
Usage: | Communication Relay |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
· monitoring of 3-phase mains:
- voltage in 2 levels (undervoltage and overvoltage) in range 120-277V(3P+N) or 208-480 V (3P3W)
- phase asymmetry (can be switched off)
- phase sequence
- phase failure
· function of second relay (independent / parallel)
· adjustable delay for short peaks for each level independently
· M480: for circuits 3x 400 V (without neutral)
· M277: for circuits 3x 400 / 230 V (with neutral)
· galvanically separated supply voltage AC 400 V, AC 110 V, AC 230 V, AC/ DC 24 V
· output contact: 2x changeover 10A / 250V AC1
· 2-MODULE, DIN rail mounting
|
DV3-01~11/M480
|
DV3-01~11/M277
|
Supply
|
||
Supply terminals
|
L1/L2/L3
|
L1/L2/L3/N
|
Supply voltage
(AC 50 - 60 Hz)
|
208-220-230-240-380
400-415-440-460-480
|
120-127-132-138-220
230-240-254-265-277
|
Consumption max.
|
5 VA / 2.5W(AC 110 V, AC 230V, AC 400 V),
2VA/1.4W (AC/DC 24V)
|
|
Max. dissipated power
(Un + terminals)
|
6.5 W (110 V, 230 V, 400 V),
5.5 W (24 V)
|
|
Supply voltage tolerance
|
- 15%;+10%
|
|
Measuring circuit
|
||
Voltage set
|
3x 400 V / 50 - 60 Hz
|
3x 400 V / 230 V / 50 - 60 Hz
|
Monitored terminals
|
L1, L2, L3
|
L1, L2, L3, N
|
Upper voltage level
|
240 - 480 V
|
138 - 276 V
|
Bottom voltage level
|
35-99% Umax
|
|
Max. permanent overload
|
3x 480 V
|
|
Hysteresis
|
2 % of set value
|
|
Asymmetry
|
5 - 20%
|
|
Peak overload < 1 ms
|
600 V < 1 ms
|
350 V < 1 ms
|
Time delay t1
|
fixed, max 200 ms
|
|
Time delay t2
|
adjustable 0.1-10 s
|
|
Accuracy
|
||
Set. accuracy (mechanical)
|
5 %
|
|
Repeat accuracy
|
< 1 %
|
|
Temperature dependance
|
< 0. 1 % / °C (°F)
|
|
Limit values tolerance
|
5 %
|
|
Output
|
||
Number of contacts
|
1x changeover / SPDT
|
|
Rated current
|
10A / AC1
|
|
Switching capacity
|
2500 VA / AC1, 240W / DC
|
|
Inrush current
|
12 A / < 3 s
|
|
Switching voltage
|
250V AC1 / 24V DC
|
|
Mechanical life
|
3x10^7
|
|
Electrical life (AC1)
|
0.7x10^5
|
|
Other informatio
|
||
Operating temperature
|
- 30 °C to 70 °C
|
|
Storage temperature
|
- 45 °C to 85 °C
|
|
Electrical strength
|
4kV (supply - output)
|
|
Operating position
|
any
|
|
Mounting
|
DIN rai EN 60715
|
|
Protection degree
|
IP40 from front panel/IP20 terminals
|
|
Overvoltage category
|
III.
|
|
Pollution degree
|
2
|
|
Max. cable size (mm^2)
|
solid wire max. 1x 2.5 or 2 x 1.5 /
with sleeve max. 2x 1.5 (AWG 14 )
|
|
Dimensions
|
90x36x70mm
|
|
Weight
|
135g
|
130g
|
Standards
|
IEC60947-5-1 EN 60255-6, EN 61010-1
|
|
Packing Details
|
Box DIM: 520x225x175, QTY: 50Pcs, GW:7.6kg
|
Relay is designated to monitor 3-phase circuits. Type N230 controls voltage towards neutral wire, type A400 controls inter phase voltage. Relay can monitor voltage in two levels (overvoltage / undervoltage), phase asymetry, phase sequence and phase failure. Each faulty state is indicated by individual LED.