DV2-01 Winston Programmable Complete Monitoring 3-Phase Mains Voltage Monitor Relay
| Customization: | Available |
|---|---|
| Theory: | Voltage Relay |
| Usage: | Communication Relay |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Find Similar Products
Basic Info.
- Model NO.
- DV2-01
- Phase
- 3
- Electricity Type
- Ac
- Size
- Miniature
- Type
- Electric Parameter Relay
- Supply Voltage
- A380:380V, A440:400V, A415:415V(P-P)
- Monitored Terminals
- L1, L2, L3, N
- Upper Voltage Level
- a:240-480V,N:138-276V
- Max. Permanent Overload
- 3X 480 V
- Switching Voltage
- 250VAC1/24VDC
- Operating Temperature
- -30°c to+70°c
- Operating Position
- Any
- Pollution Degree
- 2
- Dimensions
- 90*36*70mm
- 87*45*77.5mm
- A135g/N130g
- Transport Package
- Export Standard Carton Box or ODM
- Specification
- 87*45*77.5mm
- Trademark
- Winston/OEM/Neutral
- Origin
- China, Zhejiang, Wenzhou
- Production Capacity
- 10000PCS/Week
Product Description
· monitoring of 3-phase mains:
- voltage in 2 levels (undervoltage and overvoltage) in range 120-277V(3P+N) or 208-480 V (3P3W)
- phase asymmetry (can be switched off)
- phase sequence
- phase failure
· function of second relay (independent / parallel)
· adjustable delay for short peaks for each level independently
· M480: for circuits 3x 400 V (without neutral)
· M277: for circuits 3x 400 / 230 V (with neutral)
· galvanically separated supply voltage AC 400 V, AC 110 V, AC 230 V, AC/DC 24 V
· output contact: 2x changeover 10A / 250V AC1
· 2-MODULE, DIN rail mounting

|
|
DV2-01~10/A***
|
DV2-01~10/N***
|
|
Supply
|
||
|
Supply terminals
|
L1/L2/L3
|
L1/L2/L3/N
|
|
Supply voltage
(AC 50 - 60 Hz)
|
A380:380V, A440:400V,
A415:415V (P-P)
|
N220:220V, N230:230V, N240:240V(P-N)
|
|
Consumption max.
|
5 VA / 2.5W(AC 110 V, AC 230V, AC 400 V),
2VA/1.4W (AC/DC 24V)
|
|
|
Max. dissipated power
(Un + terminals)
|
6.5 W (110 V, 230 V, 400 V),
5.5 W (24 V)
|
|
|
Supply voltage tolerance
|
- 15%;+10%
|
|
|
Measuring circuit
|
||
|
Voltage set
|
3x 400 V / 50 - 60 Hz
|
3x 400 V / 230 V / 50 - 60 Hz
|
|
Monitored terminals
|
L1, L2, L3
|
L1, L2, L3, N
|
|
Upper voltage level
|
240 - 480 V
|
138 - 276 V
|
|
Bottom voltage level
|
35-99% Umax
|
|
|
Max. permanent overload
|
3x 480 V
|
|
|
Hysteresis
|
2 % of set value
|
|
|
Asymmetry
|
5 - 20%
|
|
|
Peak overload < 1 ms
|
600 V < 1 ms
|
350 V < 1 ms
|
|
Time delay t1
|
fixed, max 200 ms
|
|
|
Time delay t2
|
adjustable 0.1-10 s
|
|
|
Accuracy
|
||
|
Set. accuracy (mechanical)
|
5 %
|
|
|
Repeat accuracy
|
< 1 %
|
|
|
Temperature dependance
|
< 0. 1 % / °C (°F)
|
|
|
Limit values tolerance
|
5 %
|
|
|
Output
|
||
|
Number of contacts
|
1x changeover / SPDT
|
|
|
Rated current
|
10A / AC1
|
|
|
Switching capacity
|
2500 VA / AC1, 240W / DC
|
|
|
Inrush current
|
12 A / < 3 s
|
|
|
Switching voltage
|
250V AC1 / 24V DC
|
|
|
Mechanical life
|
3x10^7
|
|
|
Electrical life (AC1)
|
0.7x10^5
|
|
|
Other informatio
|
||
|
Operating temperature
|
- 30 °C to 70 °C
|
|
|
Storage temperature
|
- 45 °C to 85 °C
|
|
|
Electrical strength
|
4kV (supply - output)
|
|
|
Operating position
|
any
|
|
|
Mounting
|
DIN rai EN 60715
|
|
|
Protection degree
|
IP40 from front panel/IP20 terminals
|
|
|
Overvoltage category
|
III.
|
|
|
Pollution degree
|
2
|
|
|
Max. cable size (mm^2)
|
solid wire max. 1x 2.5 or 2 x 1.5 /
with sleeve max. 2x 1.5 (AWG 14 )
|
|
|
Dimensions
|
90x36x70mm
|
|
|
Weight
|
135g
|
130g
|
|
Standards
|
IEC60947-5-1 EN 60255-6, EN 61010-1
|
|
|
Packing Details
|
Box DIM: 520x225x175, QTY: 50Pcs, GW:7.6kg
|
|



Relay is designated to monitor 3-phase circuits. Type N230 controls voltage towards neutral wire, type A400 controls inter phase voltage. Relay can monitor voltage in two levels (overvoltage / undervoltage), phase asymetry, phase sequence and phase failure. Each faulty state is indicated by individual LED.
Time delays t1(fixed) - when changing from faulty to normal state or when de-energized and t2 when changing from normal to faulty state. These delays prevent incorrect conduct and oscillation of output device during short voltage peaks in the main or during gradual voltage decline into normal.
Set upper level Umax in range Us×(1+5%)-Us×(1+30%) and lower level Umin in range Us×(1-5%)-Us×(1-30%) Umax. In case any phase passes this range, after a delay which eliminated short voltage peaks, contact opens. Output contact again switches after returning back into monitored voltage range and exceeding ?xed hysteresis . In case of failure of two or three phases, the relay is deactivated immediately regardless of the set delay t2.
Monitors correctness of phase sequence. In case of unwanted change output contact breaks. In case of energization of a device with incorrect phase sequence, contact stays opened.
Rate of assymetry between individual phases is set in a range of 5-15 %. In case set asymmetry is exceeded, output relay breaks and LED indicating asymetry shines. Delays t1, t2 and hysteretic are applicable when returning to normal state.