Shunt Tripping, MCB Auxiliary Switch, Circuit Breaker Auxiliary Contact
1 Technical data
@Rated Current(In) 0.4, 1, 2, 3, 6A
@Rated Voltage(Un) 24VDC/48VDC/125VDC/230VAC/400VAC
Test |
Type |
Test Current |
Original State |
The tripping type does not release the time limit |
Result |
A |
B, C, D |
1.13In |
Cold State |
t≥1h |
No trip |
B |
B, C, D |
1.45In |
Following A Test |
t<1h |
Trip |
C |
B, C, D |
2.55In |
Cold State |
1s<t<60s In≤32A)
1s<t<120s In>32A)
|
Trip |
D |
B |
3In |
Cold State |
t≥0.1s |
No trip |
C |
5In |
No trip |
D |
10In |
No trip |
E |
B |
5In |
Cold State |
t<0.1s |
No trip |
C |
10In |
t<0.1s |
No trip |
D |
16In |
t<0.1s |
No trip |